Microcontroller-Based Design: Ensures precise monitoring and protection against voltage and current anomalies.
- Dual 3-Digit Display: Provides real-time voltage readings for accurate monitoring.
- Adjustable Settings:
- Overvoltage Protection: Settable between 220V and 280V.
- Undervoltage Protection: Settable between 140V and 210V.
- Reset/Start Delay: Adjustable from 5 to 600 seconds, allowing customization based on specific requirements.
- Trip Delays:
- Overvoltage Trip Delay: Less than 0.5 seconds.
- Undervoltage Trip Delay: 0.5 seconds for voltages ≥120V; 0.1 seconds for voltages <120V.
- Overcurrent Trip Delay: Adjustable between 5 to 600 seconds.
- Voltage Measurement Accuracy: Within 2% across the entire range.
- Output Contact: Equipped with 1 Normally Open (NO) contact.
- Mounting: Designed for DIN rail installation, facilitating easy integration into electrical panels.
- Protection Degree: Rated at IP20, suitable for indoor environments.
Applications
- Residential and Commercial Electrical Systems: Protects appliances and equipment from voltage sags, surges, and overcurrent situations.
- Industrial Equipment: Ensures machinery operates within safe voltage and current parameters, preventing potential damage.
- HVAC Systems: Safeguards heating, ventilation, and air conditioning units from electrical anomalies.
Benefits
Enhanced Equipment Longevity: By preventing exposure to harmful voltage and current levels, the RD-MVA 63A extends the lifespan of connected devices. ✔ Customizable Protection: Adjustable settings allow users to tailor protection parameters to specific needs. ✔ User-Friendly Interface: The dual display and LED indicators provide clear status updates and fault indications. ✔ Reliable Performance: Microcontroller-based design ensures accurate detection and rapid response to electrical faults.
- Rated supply voltage:
AC 220V
-
Operation voltage range:
AC 100V~400V
-
Rated frequency:
50/60Hz
-
Overvoltage(U>)setting range:
220~280V
-
Undervoltage(U<) setting range:
140~210V
-
Hysteresis:
﹥U:5V; <U:3V
-
Reset/start delay:
Ts: 5s~600s
-
Overcurrent faults trip delay range:
Ta: 5s~600s
-
Overvoltage(U>) trip delay:
<0.5s
-
Undervoltage(U<) trip delay:
≥120V:0.5s,<120V: 0.1 s
-
Overcurrent(l>) trip delay:
ln<lr *<lmax: Ta; Ir *≥lmax:≤0.1s
-
Voltage measurement accuracy:
2%(over the whole range)
-
Rated insulation voltage:
400V
-
Output contact:
1NO
-
Protection degree: IP20
-
Altitude: 2000m